Heating Degree Day Energy Calculator

Estimate seasonal space-heating energy from a constant UA and heating degree days. Compare SI/US results and review the method, assumptions and related references below.

Change any input to update the calculation. Unit changes preserve the physical quantity.

CALCULATION SETUP

Inputs

Need an input value?
R-Value & U-Value Conversion Chart ↗Thermal Conductivity & Layer R Reference ↗UA sums assembly U×area and applicable losses. Layer R alone is not whole-building UA.

Entered seasonal COP or useful/output efficiency fraction; 0.90 for 90%, 3 for seasonal COP 3.

Calculated locally in your browser. No sign-up or input upload.

CALCULATED VALUE

Results

Estimated useful heating energy

7,200 kWh24.5674 MMBTU

Input energy

2,400 kWh8.1891 MMBTU

Effective UA

150 W/K284.3451 BTU/(h·°F)

Input-energy cost

480 local currency

Calculation breakdown

Result interpretation
Estimate seasonal space-heating energy from a constant UA and heating degree days

Only the result summary and canonical link are shared. Inputs and free-form names are excluded.

Assumptions & checks

Constant-UA degree-day approximation using your climate period and building balance point. Solar/internal gains, varying infiltration, schedules and DHW are not separately modeled; not peak-load sizing.

Verify inputs & continue

Heat transfer/energy/cost remains continuous. Reference material conductivity, assembly R/U and seasonal performance must match actual conditions.

Use data for the actual component and operating conditions. Continue with the related calculations below after reviewing the selected result.

Formula

Estimate seasonal space-heating energy from a constant UA and heating degree days

Euseful(J)=UA(W/K)×HDD(K·day)×86400; Einput=Euseful/entered seasonal performance. Reverse UA=Euseful/(HDD×86400). Worked example: UA 150 W/K and 2000 K·day gives 7200 kWh useful heat; performance factor 3 gives 2400 kWh input and 480 at tariff 0.20.

Worked example

Using the default values shown in the calculator, the same formula gives the following result. This is a quick sanity check for the calculation, not a design recommendation.

Inputs

Effective heat-loss coefficient UA
150 W/K
Heating degree days (matching balance point)
2000 K·day
Seasonal delivered heat / input energy
3
Input-energy price per kWh
0.2

Result

Estimated useful heating energy
7,200 kWh
Input energy
2,400 kWh
Effective UA
150 W/K
Input-energy cost
480 local currency

Related calculators

Continue your workflow with a related calculation.

View all HVAC & Energy calculators

Frequently asked questions

What does this result tell me?

Constant-UA degree-day approximation using your climate period and building balance point. Solar/internal gains, varying infiltration, schedules and DHW are not separately modeled; not peak-load sizing.

How can I check the calculation?

Worked example: UA 150 W/K and 2000 K·day gives 7200 kWh useful heat; performance factor 3 gives 2400 kWh input and 480 at tariff 0.20. Review each stated input and unit; use project-specific values rather than treating the editable example as a requirement.