Electrical

Battery Runtime Calculator

Estimate battery runtime or required amp-hour capacity for a constant load. Compare SI/US results and review the method, assumptions and related references below.

Change any input to update the calculation. Unit changes preserve the physical quantity.

CALCULATION SETUP

Inputs

V
Ah
Need an input value?
Single & Three-Phase Power Reference ↗AC load real power only; battery supply voltage/capacity remain your inputs.
%
%
%

Calculated locally in your browser. No sign-up or input upload.

YOUR CALCULATION

Results

Estimated runtime

3.888 h233.28 min

Required / entered capacity

100 Ah

Nominal stored energy

1.2 kWh

Useful load energy

0.7776 kWh

Useful load power

200 W

Battery-side power

222.2222 W

Calculation breakdown

Result interpretation
Estimate battery runtime or required amp-hour capacity for a constant load

Assumptions & checks

Nominal-energy estimate; discharge curves, Peukert effect, aging, temperature, voltage sag and startup surges excluded. Verify manufacturer discharge data.

Formula

Estimate battery runtime or required amp-hour capacity for a constant load

Useful energy=V·Ah·3600·DoD·(1−reserve)·η; runtime seconds=useful joules/load watts. Reverse Ah=runtime·load/(3600·V·usable fraction). Worked example: 12 V × 100 Ah, 80% usable, 10% reserve and 90% efficiency provides 777.6 Wh to a 200 W load: 3.888 h.

Worked example

Using the default values shown in the calculator, the same formula gives the following result. This is a quick sanity check for the calculation, not a design recommendation.

Inputs

Nominal battery voltage
12 V
Nominal battery capacity
100 Ah
Load entry
Useful load power
Useful load power
200 W
Usable depth of discharge
80 %
Reserve of usable energy
10 %
Conversion efficiency
90 %

Result

Estimated runtime
3.888 h
Required / entered capacity
100 Ah
Nominal stored energy
1.2 kWh
Useful load energy
0.7776 kWh
Useful load power
200 W
Battery-side power
222.2222 W

Related calculators

Continue your workflow with a related calculation.

View all Electrical calculators

Frequently asked questions

What does this result tell me?

Nominal-energy estimate; discharge curves, Peukert effect, aging, temperature, voltage sag and startup surges excluded. Verify manufacturer discharge data.

How can I check the calculation?

Worked example: 12 V × 100 Ah, 80% usable, 10% reserve and 90% efficiency provides 777.6 Wh to a 200 W load: 3.888 h. Review each stated input and unit; use project-specific values rather than treating the editable example as a requirement.