Electrical
Battery Runtime Calculator
Estimate battery runtime or required amp-hour capacity for a constant load. Compare SI/US results and review the method, assumptions and related references below.
Change any input to update the calculation. Unit changes preserve the physical quantity.
Inputs
Calculated locally in your browser. No sign-up or input upload.
Results
Estimated runtime
3.888 h233.28 minRequired / entered capacity
100 AhNominal stored energy
1.2 kWhUseful load energy
0.7776 kWhUseful load power
200 WBattery-side power
222.2222 WCalculation breakdown
- Result interpretation
- Estimate battery runtime or required amp-hour capacity for a constant load
Assumptions & checks
Nominal-energy estimate; discharge curves, Peukert effect, aging, temperature, voltage sag and startup surges excluded. Verify manufacturer discharge data.
Formula
Estimate battery runtime or required amp-hour capacity for a constant load
Worked example
Using the default values shown in the calculator, the same formula gives the following result. This is a quick sanity check for the calculation, not a design recommendation.
Inputs
- Nominal battery voltage
- 12 V
- Nominal battery capacity
- 100 Ah
- Load entry
- Useful load power
- Useful load power
- 200 W
- Usable depth of discharge
- 80 %
- Reserve of usable energy
- 10 %
- Conversion efficiency
- 90 %
Result
- Estimated runtime
- 3.888 h
- Required / entered capacity
- 100 Ah
- Nominal stored energy
- 1.2 kWh
- Useful load energy
- 0.7776 kWh
- Useful load power
- 200 W
- Battery-side power
- 222.2222 W
Related calculators
Continue your workflow with a related calculation.
Electrical
Electrical Energy Cost Calculator
Build a multi-load energy and cost estimate with quantity, hours and duty cycle. SI/US units, clear methods and related references.
Electrical
Electrical Power Calculator
Solve electrical input power, current or supply voltage for DC and balanced AC loads. SI/US units, clear methods and related references.
Electrical
Cable Resistance Calculator
Calculate temperature-adjusted conductor resistance or solve metal area and length. SI/US units, clear methods and related references.
Technical references for this calculation
Frequently asked questions
What does this result tell me?
Nominal-energy estimate; discharge curves, Peukert effect, aging, temperature, voltage sag and startup surges excluded. Verify manufacturer discharge data.
How can I check the calculation?
Worked example: 12 V × 100 Ah, 80% usable, 10% reserve and 90% efficiency provides 777.6 Wh to a 200 W load: 3.888 h. Review each stated input and unit; use project-specific values rather than treating the editable example as a requirement.