0.5 in Type K
- Calculated nominal bore
- 13.386 mm
- Nominal / average OD
- 15.875 mm
- Source wall thickness
- 1.245 mm
More dimensions
- Product family
- Type K
- Nominal inch designation
- 0.5
- Calculated bore area
- 140.727 mm²
VALICALC · TECHNICAL REFERENCE
Compare selected Type K and L copper tube OD, wall and calculated bore in metric or inches. Keep historical dimensions separate from current product ratings.
Search within the verified subset. Numeric sizes match complete designations; a nearby size is a candidate, not an exact match.
SELECTED REFERENCE
v1.3.0 · verified 2026-10-07
Use this value
Review the selected values and units in the calculator before applying them.
Use calculated bore →Use bore in Pump TDH →Use bore in Hazen-Williams →6 matching rows · 6 in this subset
| Product / tube designation | Calculated nominal bore | Nominal / average OD | Source wall thickness | Actions |
|---|---|---|---|---|
| 0.5 in Type K | 13.386 mm | 15.875 mm | 1.245 mm | |
| 0.5 in Type L | 13.843 mm | 15.875 mm | 1.016 mm | |
| 0.75 in Type K | 18.923 mm | 22.225 mm | 1.651 mm | |
| 0.75 in Type L | 19.939 mm | 22.225 mm | 1.143 mm | |
| 1 in Type K | 25.273 mm | 28.575 mm | 1.651 mm | |
| 1 in Type L | 26.035 mm | 28.575 mm | 1.27 mm |
Retain the stated nominal size, OD and Type K/L wall. Convert inches by 25.4, derive ID=OD−2wall and circular bore area. Nominal size does not equal OD or ID.
CHECK THE METHOD
Nominal 1/2 in Type L: OD 0.625 in and wall 0.040 in give nominal ID 0.545 in = 13.843 mm; Type K at the same size has thicker wall.
Historical dimensions are an identification aid, not current product certification or a permitted-use/code determination. Verify the actual tube designation, wall and supplier drawing.
TRACEABLE DATA
Dataset v1.3.0
Last verified:
Six selected nominal dimensional examples from the historical government-published K/L table. Type M, ACR and pressure ratings are outside this verified subset.
Values are curated product facts or generated scenarios. Paid standards, complete catalogs and source diagrams are not reproduced. A verification date applies to this documented subset.
Type B · Oregon OSHA / US OSHA · Table H-24; published dimensional subset, checked 2026-10-07
Selected government-published facts and dimensional derivations; no paid-standard table reproduced.