HVAC & Energy

Air Cooling Load Calculator

Calculate sensible and latent cooling from an entered moist-air process or reverse airflow. Compare SI/US results and review the method, assumptions and related references below.

Change any input to update the calculation. Unit changes preserve the physical quantity.

CALCULATION SETUP

Inputs

Mass of vapor per mass of dry air, not relative humidity percent.

Need an input value?
Dry Air Properties Table ↗Dry-air reference is approximate for moist entering air; enter applicable moist-air density.

Calculated locally in your browser. No sign-up or input upload.

YOUR CALCULATION

Results

Total air-process cooling

19.9639 kW68,119.5918 BTU/h

Sensible cooling

10.9921 kW37,506.7454 BTU/h

Latent remainder

8.9717 kW30,612.8464 BTU/h

Sensible heat ratio

0.5506

Volume flow

500 L/s30,000 L/min1,800 m³/h7,925.1616 GPM (US)1,059.44 CFM

Ideal condensed moisture

12.7811 kg/h

Entering enthalpy

68.0393 kJ/kg dry air

Leaving enthalpy

34.3003 kJ/kg dry air

Calculation breakdown

Result interpretation
Calculate sensible and latent cooling from an entered moist-air process or reverse airflow

Assumptions & checks

Entered air-process estimate, not building cooling load or equipment selection. Model range 0–60°C; supersaturated states rejected. Condensate sensible enthalpy and coil bypass are excluded.

Formula

Calculate sensible and latent cooling from an entered moist-air process or reverse airflow

h=1.006T+w(2501+1.86T) kJ/kg dry air; mdry=ρmoistQ/(1+wenter); Ptotal=mdry(henter−hleave). Psensible=mdry(1006+1860wenter)ΔT. Condensate=mdryΔw. Worked example: 500 L/s, 1.2 kg/m³, 32°C/14 g/kg entering and 14°C/8 g/kg leaving gives approximately 20.20 kW and 12.78 kg/h condensate.

Worked example

Using the default values shown in the calculator, the same formula gives the following result. This is a quick sanity check for the calculation, not a design recommendation.

Inputs

Entering air volume flow
500 L/s
Entering air temperature
32 °C
Leaving air temperature
14 °C
Entering humidity ratio
14 g/kg dry air
Leaving humidity ratio
8 g/kg dry air
Entering moist-air density
1.2 kg/m³
Atmospheric pressure
101.325 kPa

Result

Total air-process cooling
19.9639 kW
Sensible cooling
10.9921 kW
Latent remainder
8.9717 kW
Sensible heat ratio
0.5506
Volume flow
500 L/s
Ideal condensed moisture
12.7811 kg/h
Entering enthalpy
68.0393 kJ/kg dry air
Leaving enthalpy
34.3003 kJ/kg dry air

Related calculators

Continue your workflow with a related calculation.

View all HVAC & Energy calculators

Frequently asked questions

What does this result tell me?

Entered air-process estimate, not building cooling load or equipment selection. Model range 0–60°C; supersaturated states rejected. Condensate sensible enthalpy and coil bypass are excluded.

How can I check the calculation?

Worked example: 500 L/s, 1.2 kg/m³, 32°C/14 g/kg entering and 14°C/8 g/kg leaving gives approximately 20.20 kW and 12.78 kg/h condensate. Review each stated input and unit; use project-specific values rather than treating the editable example as a requirement.

Reference data & method sources

VALICALC · PRIVACY